Installation Guide
Bacharach HGM300 to Johnson Metasys N2
Communications Adapter
Electrically Isolated N2 Port Version
Introduction
The Bacharach HGM300 to Johnson Metasys N2 Communcations Adapter enables an
HGM300 Refrigerant Monitor to communicate with a Metasys building management
system. Zone PPM readings, flow status, refrigerant selections, and HGM internal health
may be viewed on Metasys operator stations. In addition, each HGM zone supports three
levels of alarming (Leak, Spill, Evacuate) through Metasys and each alarm threshold can
be set through Metasys.
The N2 Communications Adapter can be used in conjunction with the RDM800 remote
display if desired. Wiring details and operation limitations when using the RDM800 will
be discussed below.
Caution
The adapter is powered from the 120V Auxiliary Power connection on the HGM main
board. When the HGM is powered up, 120V is present on the lower left corner of the
adapter within the area shown on the board silkscreen. Keep fingers away from this area
when HGM is powered!!
Adapter Installation Inside HGM300
The communications adapter board will normally be installed in the HGM300 at the
factory. It can, however, be field installed by following the instructions below.
The following installation materials are needed for field installation of the adapter:
(5) 6-32 x ¼” screws (standard finish)
(5) 6-32 x ½” threaded standoffs
(5) 6-32 x ¼” decorative black anodized screws (standard finish OK, black looks nicer)
1 of 10
Vista de pagina 0
1 2 3 4 5 6 7 8 9 10

Indice de contenidos

Pagina 1

3015-4570 Revision 1.1 8/6/03 Installation Guide Bacharach HGM300 to Johnson Metasys N2 Communications Adapter Electrically Isolated N2 Port Versio

Pagina 2

Communications LED Indicators See Figure 4 for the locations of the communications LED indicators. The communications adapter board has four LED com

Pagina 3

The adapter board mounts on the rear of the HGM300 door. Position the adapter board so as not to interfere with the HGM internal components when the

Pagina 4

If an RDM800 remote display is NOT used with the adapter, refer to Figure 2 for wiring details. In this case, all wiring between the HGM300 main boar

Pagina 5

If an RDM800 remote display IS to be used with the adapter, refer to Figure 3 for wiring details. Note that when the RDM800 is used, TWO RS-485 cable

Pagina 6

Field Hookup of N2 Communications The “BAS BUS” (N2) RS-485 communications port on the adapter is electrically isolated from the HGM300 and from eart

Pagina 7

6 of 10

Pagina 8

Setting Metasys N2 Address On Communication Adapter Switches 1-8 on the adapter’s ‘B’ dipswitch are used to set the Metasys N2 node address. Possibl

Pagina 9

Configuring the HGM300 with RDM800 or Laptop PC The only HGM parameters that are changeable through Metasys are the alarm thresholds. Configuring th

Pagina 10

There are several ADI points which can provide useful information such as type of refrigerant programmed for each zone, number of zones actually insta